1.2 DECArray300 Specifications
Table 1–6 DECArray300 Cabinet System Electrical Specifications
Voltage 120 Vac 240 Vac
Voltage range nominal 100–120 Vac 220–240 Vac
Input Voltage functional range 86–132 Vac 174–264 Vac
Inrush Current 235 A 150 A
AC–Plug type NEMA L5–30P P/N 12–14379–03
Power Controller 874 887–D
Circuit Breaker 30 A 16 A
Rated Current: 24 A 12 A
Typical Current:
Tx8xx 1.73 A 0.9 A
Sx7x 2.22 A 1.5 A
Rx9x 3.6 A 1.8 A
Power Factor 0.6 0.6
Typical current at nominal voltage. In order to calculate the typical current
of the Sx300 storage array, add the typical current of the storage elements.
The maximum current of the storage array can be up to 20 percent higher
compared with the nominal current.
The ride-through time is > 20 ms. That means that a voltage drop below the
minimum functional voltage range up to 20 ms will not have any impact on the
functionality of the array.
Note
A time lag fuse for the main voltage must be used to avoid the inrush
current blowing the fuse.
Table 1–7 and 1–8 list the recommended environmental operating ranges and
recommended environmental limits for the DECArray300 cabinet system.
1–8 General Information