1.2 DECArray300 Specifications
Table 1–7 Cabinet System Environmental Operating Range
Characteristic Specification
Agency compliance UL, CSA, and TUEV*
Temperature +10°C to +40°C (+50°F to +104°F).
Derate 1.8°C for each 1000 meters altitude
(1.0°F for each 1000 feet altitude)
Humidity 10% to 85% @ maximum wet bulb
temperature of +32°C (+90°F) and minimum
dew point of +2°C (+36°F)
Note
*TUEV approval is only granted for the 220/240 Vac version storage
cabinets produced in Digital’s Kaufbeuren Manufacturing Plant (for
Europe).
Table 1–8 Cabinet System Recommended Environmental Conditions
Operating environment Specification
Temperature 18°C to 24°C (64.4°F to 75.2°F) with an
average rate of change of 3°C/hour maximum
and a step change of 3°C or less
Relative humidity 40% to 60% (noncondensing) with a step
change of 10% or less (noncondensing)
Altitude Up to 2400 meters (8000 feet)
Air quality (maximum
particle count)
Not to exceed 500,000 particles per cubic foot
of air at a size of 0.5 micron or larger
Air volume (at inlet) 50 cubic feet per minute (0.026 cubic meters
per second)
General Information 1–9